產品中心
HYDAC變送器無輸出時怎樣調解
HYDAC變送器無輸出時怎樣調解HYDAC賀德克變(bian)(bian)送(song)(song)器如果由(you)兩個(ge)用來測量溫差的傳感器組成,輸出信(xin)號與溫差之(zhi)間有(you)一給定的連續函數關(guan)系(xi)。故稱為溫度變(bian)(bian)送(song)(song)器。
HYDAC變送器無輸出時怎樣調解
HYDAC賀德克變送器如(ru)果(guo)由兩個用來測(ce)量(liang)溫(wen)差(cha)的(de)(de)(de)傳(chuan)(chuan)感(gan)器(qi)組(zu)成,輸(shu)(shu)出信(xin)(xin)號(hao)與溫(wen)差(cha)之(zhi)間(jian)有(you)一給定的(de)(de)(de)連續(xu)函數關(guan)系。故稱為溫(wen)度(du)變(bian)(bian)(bian)送(song)器(qi)。HYDAC溫(wen)度(du)變(bian)(bian)(bian)送(song)器(qi)輸(shu)(shu)出信(xin)(xin)號(hao)與溫(wen)度(du)變(bian)(bian)(bian)量(liang)之(zhi)間(jian)有(you)一給定的(de)(de)(de)連續(xu)函數關(guan)系(通常為線(xian)性函數),早期生產的(de)(de)(de)變(bian)(bian)(bian)送(song)器(qi)其輸(shu)(shu)出信(xin)(xin)號(hao)與溫(wen)度(du)傳(chuan)(chuan)感(gan)器(qi)的(de)(de)(de)電(dian)(dian)阻(zu)值(zhi)(或電(dian)(dian)壓值(zhi))之(zhi)間(jian)呈線(xian)性函數關(guan)系。溫(wen)度(du)變(bian)(bian)(bian)送(song)器(qi)的(de)(de)(de)供電(dian)(dian)電(dian)(dian)源(yuan)不得有(you)尖(jian)峰,否(fou)則容易(yi)損壞變(bian)(bian)(bian)送(song)器(qi)。變(bian)(bian)(bian)送(song)器(qi)的(de)(de)(de)校準應在加電(dian)(dian)5分鐘后進(jin)行,并且要注意當時環境(jing)溫(wen)度(du)。測(ce)高溫(wen)時(>>100℃)傳(chuan)(chuan)感(gan)器(qi)腔(qiang)與接線(xian)盒間(jian)應用填充(chong)材料(liao)隔離,防(fang)止接線(xian)盒溫(wen)度(du)過高燒壞變(bian)(bian)(bian)送(song)器(qi)。在干擾嚴重的(de)(de)(de)情況下使用傳(chuan)(chuan)感(gan)器(qi),外殼應牢固接地避免干擾,電(dian)(dian)源(yuan)及信(xin)(xin)號(hao)輸(shu)(shu)出應采用Ф10屏蔽電(dian)(dian)纜傳(chuan)(chuan)輸(shu)(shu),壓線(xian)螺母(mu)應旋緊以保證氣(qi)密性。
HYDAC賀德克變送器無輸出
①賀德克HYDAC變送器無輸出,檢查賀德克HYDAC變送器電源是不是接反;
把電源極性接;
②丈量HYDAC變送器的供電電源,是不是有24V直流電壓;
有必要保證供給賀德克HYDAC變送器的電源電壓≥12V(即賀德克HYDAC變送器電源輸入端電壓≥12V)。假設沒有電源,則應檢查回路是不是斷線、檢查表面是不是挑選過錯(輸入阻抗應≤250Ω);等等。
③假設是一體化帶表頭的,檢查表頭是不是損壞(可以先將表頭的兩根線短路,假設短路后正常,則說明是表頭損壞);
表頭損壞的則需另換表頭;
④將電流表串入24V電源回路中,檢查電流是不是正常;
假設正常則說明賀德克HYDAC變送器正常,此時應檢查回路中其他表面是不是正常。賀德克HYDAC變送器輸出精度不合懇求;
1、HYDAC變送器電源是不是正常
假設小于12VDC,則應檢查回路中是不是有大的負載,賀德克HYDAC變送器負載的輸入阻抗應符合RL≤(賀德克HYDAC變送器供電電壓-12V)/(0.02A)Ω
2、是不是進行過一體化調試
進行一體化調試
3、熱電阻(或熱電偶)與外殼絕緣是不是抵達懇求
如絕緣(yuan)不合懇求,則需進行相應的絕緣(yuan)處理。
HYDAC變送器無輸出時怎樣調解